Size a booster pump for the water flow needed at the same time and the additional head required to deliver that flow at the outlets. The starting information is the simultaneous demand, required outlet pressure, elevation, pipework losses and minimum available inlet conditions. A motor’s HP rating or a pump’s advertised maximum flow cannot answer that question alone.
First identify the supply arrangement: water drawn from a storage tank, or pressure added to an existing pressurised supply. These use different inlet references. A pump can add head, but it cannot make up for an inlet source that cannot supply enough water.
Add the demands that must run together
List the outlets that are expected to operate simultaneously and their required flow rates. Use the actual appliance or fixture information where available. A shower, irrigation zone and washing machine may have very different flow and pressure requirements.
For a simple planning example, assume two showers each need 9 L/min and one tap needs 6 L/min, all running together:
Design flow = 9 + 9 + 6 = 24 L/min = 1.44 m³/h.
These are teaching assumptions, not standard fixture allowances. Substitute the intended fixtures and a credible use pattern. For larger buildings, use an appropriate demand assessment instead of adding every outlet as though all operate continuously, or inventing a diversity percentage.
Daily consumption helps check storage and source replenishment. It does not establish the instantaneous flow needed when several outlets open together. A tank can contain enough water for the day while an undersized delivery pump still struggles with the morning peak.

Work backwards from the critical outlet
Choose the outlet or operating combination that is hardest to supply. That may be the highest outlet, a long pipe route or an appliance with a higher pressure requirement. Check the other operating combinations as well.
At the selected design flow, account for the required residual pressure at that outlet, the elevation difference and the losses through the relevant pipework, fittings and equipment. Residual pressure is the pressure still needed there while water is flowing. It is not the pump’s shutoff pressure.
Use consistent units: for ordinary water, 1 bar is approximately 10.2 m of head. The DAB pump-selection guide separates geometric lift, required pressure and losses when establishing the required head. Actual fixture requirements and route losses must replace generic allowances.
Losses depend on flow and the real pipe route. Calculate the common supply section at its combined flow and each branch at the flow it carries. Include restrictions such as filters and treatment equipment at the design condition; a clean-filter pressure drop may not describe the permitted service limit.
Use the correct inlet reference
Water supplied from an open storage tank
Use the lowest intended operating water level in the vented tank as the starting free surface. Its elevation relative to the pump matters. A full-tank water level can make an unsuitable installation look better than it will be near the low-level stop point.
For this reference, a simplified required pump head is:
Head to add = outlet elevation above the pump + required outlet pressure head + inlet-and-delivery losses − tank water level above the pump.
The formula assumes the tank surface is above the pump. If it is below, the signed elevation makes that contribution increase the required head, and the installation also needs a separate suction and priming assessment. Tank capacity, refill rate and low-water protection must support the intended demand.
A pressurised supply connected to the pump inlet
Use the minimum inlet pressure available at the required flow, referenced to the pump inlet. A static gauge reading with all outlets shut can overstate the pressure available during peak use.
With this reference, add the outlet pressure requirement, elevation above the pump and downstream losses, then subtract the available dynamic inlet pressure head. Inlet pipe losses upstream of that pressure reading are already reflected in it; do not add those upstream losses again or also credit an upstream tank’s full elevation.
Grundfos explains booster inlet pressure and pressure increase using the required delivery pressure and minimum inlet pressure. Check both the minimum and maximum supply conditions. For a direct utility connection, establish the water supplier’s connection and backflow requirements when deciding between direct boosting and a storage or break-tank arrangement.
Worked example: 24 L/min from an open tank
Assume the three-outlet demand above is supplied from a vented tank. The pump centreline is the elevation datum. The lowest operating tank surface is 2 m above it, and the critical outlet is 8 m above it.
For this example only, the outlet requires 2.0 bar while flowing, equivalent to about 20.4 m of head. Assume a combined 6 m allowance for inlet and delivery pipework losses under the simultaneous demand. This is a stated assumption, not a pipe-size calculation or a universal percentage.
Required additional head = 8 + 20.4 + 6 − 2 = 32.4 m.
The resulting planning point is approximately 1.44 m³/h at 32 m of pump head. The 2 m credit comes from the tank’s minimum free-surface elevation. It is not an independently measured inlet-pressure value to subtract a second time.

Use this as a simplified selection estimate. The supplier or installer must confirm the actual losses, outlet requirements and final duty point. A lower tank level, different simultaneous demand or longer pipe route changes the result.
Find that point on the pump curve
Read flow and head together on the candidate pump’s curve for the intended speed or control mode. Check the manufacturer’s permitted operating range around the required point and the expected range of demand. The Hydraulic Institute explains how system head and piping losses determine the operating point.
Maximum head is normally associated with little or no flow; maximum flow is achieved at a much lower head. A pump advertised with a maximum flow above 24 L/min and maximum head above 32 m may still fail to deliver those two values together. Confirm the head available at the required flow.
After the hydraulic match, check the motor supply and starting requirements. For the same motor power, different pump designs can have different flow/head characteristics. Selecting a larger motor label is not a substitute for checking the curve.
Check inlet supply, suction conditions and maximum pressure
Confirm that the inlet can supply the design flow for the intended operating period. If the source falls short, a larger booster may draw the tank down faster or worsen inlet conditions. Storage and source replenishment need their own assessment.
For a surface pump, check available suction conditions against the selected pump’s requirements, including inlet losses, minimum tank level, water temperature and site elevation. KSB’s NPSH explanation distinguishes the suction head available from the system and the head required by the pump. A universal suction-lift claim is insufficient for an actual installation; a flooded inlet still needs adequate available NPSH.
Also check the highest possible system pressure. Maximum inlet pressure plus the pump’s pressure rise near shutoff can exceed the normal operating pressure. The pump, controller, tank, pipework and connected equipment must remain within their ratings. The Grundfos Hydro MPC instructions explicitly require checking minimum and maximum inlet conditions; use the selected equipment’s own limits rather than transferring that product’s ratings.
Match the controls to the water demand
A pressure switch with a suitable pressure tank, a fixed-speed pressure/flow controller and a variable-speed pressure system have different operating behaviours. Select the control arrangement after establishing the hydraulic requirements, including the smallest normal demand and permitted pump starting frequency.
An electronic on/off controller does not automatically provide variable-speed constant pressure. A variable-speed system also needs a compatible motor, appropriate sensing and a workable low-demand strategy. Confirm source protection, motor protection and the behaviour after water loss or power restoration.
Information to send for a booster selection
| Selection input | What to provide |
|---|---|
| Simultaneous demand | Outlets or zones that run together, their required flows and operating pattern. |
| Critical outlet requirement | Required flowing pressure, elevation and route; include appliance requirements. |
| Inlet arrangement | Tank supply or pressurised inlet, minimum and maximum conditions, and available flow. |
| Pipework and equipment | Actual internal pipe sizes, route lengths, fittings, filters and treatment pressure losses. |
| Electrical supply and control | Voltage, phase, frequency, desired control behaviour and relevant motor details. |
| Storage and protection | Usable storage, refill ability, low-water stop and required reset behaviour. |
For a new enquiry, use QDD’s pressure-boosting application requirements to organise these inputs. Request the proposed curve point and the inlet, control and protection assumptions alongside the quotation.
At commissioning, verify delivery flow and pressure under the agreed simultaneous demand, then check the smallest demand and the approved stop/protection sequence. Record the results and settings so future changes can be assessed against the original selection.